扬州市红旗电缆制造有限公司
Yangzhou Hongqi cables manufacturing Co., LTD
Cable technical parameters
A. The rated voltage Uo/U is 0.6/1kV
B. Usage characteristics: 1. The cable load working environment temperature range is -15℃~+70℃, the conductor maximum working temperature is +90℃;
2. The minimum bending radius of the cable when laying:
Cable structure characteristics
|
Cable outer diameter D
|
Minimum bend radius
|
Metal braided armor type
|
Any value
|
6D
|
Non-armored type
|
D<=25
|
4D
|
D > 25
|
6D
|
C. The structure and characteristics of the cable (parameters are listed in the table below) :
1. Model CEFR/SA
1. Reference standard:
1.1 Structure: IEC60092-350, IEC60092-353
1.2 Conductor: IEC60228, Class 5
1.3 Insulation: IEC60092-360
1.4 Sheath: IEC60092-360
Flame retardant performance: IEC60332-3-22
1.6 The maximum operating temperature of the
conductor is 90℃
2、 Structure Description
2.1 Conductor: tinned copper wire
2.2 Insulation: EPR-ethylene-propylene insulation
2.3 Filling: high temperature and flame retardant filling (if required)
2.3 Outer sheath: chlorinated polyethylene rubber